H2S
Gas | Hydrogen Sulfide |
Formula | H2S |
CAS number | 7783-06-4 |
Max. workplace concentration | 5 ppm |
Relative density | 1.19 |
Appearance | Colorless Smell of rotten eggs |
Hazards | Toxic, nausea, respiratory paralysis |
The ME1250 Gas Sensor is a remote measuring unit for monitoring gas concentration of hydrogen sulphide. This gas is known for the smell of rotten eggs and blocks the olfactory nerves after some time. After a while, the gas can no longer be smelled, and therefore poses a particular risk.
The microprocessor-controlled electronics of the sensor, adapted to the specific properties of the measuring cell, enable fast and reliable signal processing. The measured gas con-centration is transmitted to a Gas Control Panel, which can manage a large number of distributed gas sensors.
Thanks to bus communication, only one cable is required, which can be continued from sensor to sensor. The ME 1250 Gas Sensor is also available with an analogue output signal of 4…20 mA. The measured gas concentration can thereby be processed by other PLC (Programmable Logic Controllers).
The optional relay module expands the ME 1250 Gas Sensor internally with 3 relays for direct switching of signal transmitters without the use of a control panel.
Advantages
- Automatic zero point calibration
- Active noise reduction on the measurement signal
- Linear measurement signal depending on the gas concentration
- High response sensitivity with short response time
- Selective and reliable measurement with a stable measurement signal and zero point
- Temperature-compensated measurement signal
- Long service life
Technical Specifications
Versions
Article code | 12BUS-H2S-51 | 1250-H2S-51 |
---|---|---|
Description | Gas Sensor ME 1250 H2S Hydrogen Sulphide Bus communication | Gas Sensor ME 1250 H2S Hydrogen Sulphide Analogue |
Output signal | Bus communication with gas control panel | Analogue 4…20 mA Load max. 800 Ω at 24V input |
Connection | 4-core cable U72M 1x4x0.6 mm Shielded | 3-core cable U72M 1x4x0.6 mm or CY 0.5 mm2 Shielded |
Topology | Bus, tree or star topology | Star topology |
Power | < 0.15 W | < 0.8 W |
Signal Processing
Accessories
Article Code | Description |
1250-REL | Relay module for single sensor ME 1250 |
1250-AIR-BOX | Ventilation duct add-on box for gas sensor ME 1250 |
1250-AIR-FLOW | Fitting hose connection for gas sensor ME 1250 |
1250-SUP | Mounting plate round pillars for gas sensor ME 1250 |
1250-SCHUTZ | Sun and weather protection for gas sensor ME 1250 |
Consumables
Article code | Description | Lifespan |
---|---|---|
CELL-H2S-C50 | Measuring cell for hydrogen sulfide | up to 2 years |
Gas concentration
- Exposure above 50 ppm requires recalibration
- Exposure above 100 ppm can destroy the measuring cell
Cross sensitivity
Gas | Concentration | Reading |
---|---|---|
Carbon Monoxide CO | 100 ppm | < 1 ppm |
Hydrogen H2 | 10,000 ppm | < 5 ppm |
Nitric Oxyde NO | 35 ppm | 2 ppm |
Nitrogen Dioxide NO2 | 5 ppm | -0.1 ppm |
Sulphur Dioxide SO2 | 100 ppm | 20 ppm |
Methanthiol | 10 ppm | ~ 5 ppm |
Tert-Butylthiol | 10 ppm | ~ 3.5 ppm |